G&D SMART / Professional outdoor lighting

System Planning

Online System Planning Tool

Calculate Your Permanent Lighting System

Enter roofline length, spacing, voltage, fixture wattage, extension cable length and wire gauge to estimate light quantity, branch load, voltage drop, last-light voltage, GC08 capacity and a preliminary BOM.

Open Permanent Lighting Calculator →

Plan the system in this order: choose voltage first, then fixture family, GC08 capacity, track and cable layout, and finally the required control-platform route.

1. Choose System Voltage

2. Choose GC08 Capacity

GC08 is available in 350W and 600W versions for each voltage architecture.

350W vs 600W GC08 Control Box Guide

3. Match the Complete BOM

Confirm the selected roofline light, model-matched track, cable and connector family, signal accessory requirements and final branch layout as one project configuration.

4. Confirm Software Route

Control platform, firmware and App capability should be confirmed against the final GC08 revision selected for the project.

Five practical system-planning answers

Compare fixture models · Compare all six Installer Kits · Request a configuration review


CONTROLLER HARDWARE REVISION · SYSTEM DESIGN RULE

Separate Standard GC08 from GC08 Pro Before Calculating a System

Platform Published architecture Planning boundary
Standard GC08 Four protected DC power outputs; 350W or 600W total-capacity versions. The product reference describes up to 150W per output where supported by the selected configuration. Verify the exact voltage, total nameplate capacity, per-output protection and approved branch limit for the supplied model. Do not assume all four outputs can each deliver 150W simultaneously.
GC08 Pro Six integrated SPI / power output ports: four ports rated up to 100W each and two ports rated up to 300W each; 600W maximum total system output. The arithmetic sum of per-port ratings is 1,000W, but available combined output remains capped at 600W. Recommended planning target is 480W total, with every port also kept within its own rating.

Keep three quantities separate

  • Power output: the electrical supply and protected load limit of each port.
  • SPI data output: the signal channel used to address and control the fixture chain.
  • Total controller capacity: the combined power limit of the exact controller hardware and power-supply configuration.

A power output count is not automatically an SPI data-channel count. Do not transfer the GC08 Pro six-port specification to the standard four-output GC08. Do not treat the sum of individual port ratings as the combined system capacity.

System Designer allocation sequence

  1. Identify the exact controller model and PCB revision: standard GC08 or GC08 Pro.
  2. Match controller voltage to the fixture family.
  3. Calculate each branch load from the exact fixture and worst-case approved operating mode.
  4. Apply the individual port limit and total system limit independently.
  5. Check branch current, wire construction and AWG, connector rating, voltage drop, end voltage and power injection.
  6. Confirm hardware protection, firmware behavior and model-specific certification before release.

GC08 product and hardware specification · Capacity planning · Class 2 documentation

GC08 Controller Planning Rule

Use the recommended 80% operating target for controller-count planning: 350W GC08 = 280W and 600W GC08 = 480W. Divide the calculated total connected load by the applicable recommended planning capacity and round up. Then distribute the load across protected outputs and verify branch current, wiring, connectors, voltage drop, power injection and certification separately.


Unified Roofline System Planning Matrix

This planning layer combines roofline length, fixture spacing, estimated fixture count, baseline load, voltage strategy, GC08 quantity and branch planning. Fixture count = floor(length in feet × 12 ÷ spacing in inches). Baseline load = fixture count × 0.96W.

GC08 planning rule: 350W GC08 = 280W recommended operating capacity; 600W GC08 = 480W recommended operating capacity. Controller quantity is based on total planning load and then rounded up. This is not a certification limit.

Length Spacing Lights Load Voltage direction GC08 planning Branch planning*
100 ft 6" 200 192.0W 24V / 36V 1×350W (≤280W) 2
100 ft 8" 150 144.0W 24V / 36V 1×350W (≤280W) 2
100 ft 9" 133 127.7W 24V / 36V 1×350W (≤280W) 2
100 ft 10" 120 115.2W 24V / 36V 1×350W (≤280W) 1
100 ft 12" 100 96.0W 24V / 36V 1×350W (≤280W) 1
100 ft 14" 85 81.6W 24V / 36V 1×350W (≤280W) 1
100 ft 16" 75 72.0W 24V / 36V 1×350W (≤280W) 1
100 ft 18" 66 63.4W 24V / 36V 1×350W (≤280W) 1
200 ft 6" 400 384.0W 24V / 36V / 48V 1×600W (≤480W) 4
200 ft 8" 300 288.0W 24V / 36V / 48V 1×600W (≤480W) 3
200 ft 9" 266 255.4W 24V / 36V / 48V 1×350W (≤280W) 3
200 ft 10" 240 230.4W 24V / 36V / 48V 1×350W (≤280W) 2
200 ft 12" 200 192.0W 24V / 36V / 48V 1×350W (≤280W) 2
200 ft 14" 171 164.2W 24V / 36V / 48V 1×350W (≤280W) 2
200 ft 16" 150 144.0W 24V / 36V / 48V 1×350W (≤280W) 2
200 ft 18" 133 127.7W 24V / 36V / 48V 1×350W (≤280W) 2
300 ft 6" 600 576.0W 36V / 48V 2×600W 3
300 ft 8" 450 432.0W 36V / 48V 1×600W (≤480W) 4
300 ft 9" 400 384.0W 36V / 48V 1×600W (≤480W) 4
300 ft 10" 360 345.6W 36V / 48V 1×600W (≤480W) 3
300 ft 12" 300 288.0W 36V / 48V 1×600W (≤480W) 3
300 ft 14" 257 246.7W 36V / 48V 1×350W (≤280W) 3
300 ft 16" 225 216.0W 36V / 48V 1×350W (≤280W) 2
300 ft 18" 200 192.0W 36V / 48V 1×350W (≤280W) 2
400 ft 6" 800 768.0W 48V preferred 2×600W 4
400 ft 8" 600 576.0W 48V preferred 2×600W 3
400 ft 9" 533 511.7W 48V preferred 2×600W 3
400 ft 10" 480 460.8W 48V preferred 1×600W (≤480W) 4
400 ft 12" 400 384.0W 48V preferred 1×600W (≤480W) 4
400 ft 14" 342 328.3W 48V preferred 1×600W (≤480W) 3
400 ft 16" 300 288.0W 48V preferred 1×600W (≤480W) 3
400 ft 18" 266 255.4W 48V preferred 1×350W (≤280W) 3
600 ft 6" 1200 1152.0W 48V preferred 3×600W 5
600 ft 8" 900 864.0W 48V preferred 2×600W 4
600 ft 9" 800 768.0W 48V preferred 2×600W 4
600 ft 10" 720 691.2W 48V preferred 2×600W 3
600 ft 12" 600 576.0W 48V preferred 2×600W 3
600 ft 14" 514 493.4W 48V preferred 2×600W 3
600 ft 16" 450 432.0W 48V preferred 1×600W (≤480W) 4
600 ft 18" 400 384.0W 48V preferred 1×600W (≤480W) 4
800 ft 6" 1600 1536.0W 48V preferred 4×600W 7
800 ft 8" 1200 1152.0W 48V preferred 3×600W 5
800 ft 9" 1066 1023.4W 48V preferred 3×600W 5
800 ft 10" 960 921.6W 48V preferred 2×600W 4
800 ft 12" 800 768.0W 48V preferred 2×600W 4
800 ft 14" 685 657.6W 48V preferred 2×600W 3
800 ft 16" 600 576.0W 48V preferred 2×600W 3
800 ft 18" 533 511.7W 48V preferred 2×600W 3

*Branch planning is a conservative system-planning aid, not a statement of the maximum permitted load per GC08 output. Final branch count and fixture distribution must follow the exact GC08 hardware, output protection, wire gauge, connector rating and certification requirements.

Power Injection / Voltage Drop Decision

  1. Calculate actual worst-case fixture load.
  2. Choose the matched system voltage and controller architecture.
  3. Calculate current for each branch.
  4. Check cable resistance, connector rating and allowable end-of-branch voltage.
  5. If the branch exceeds the approved electrical limits, split the branch or add power injection.
  6. Place injection points according to the calculated voltage-drop profile—not a generic distance rule.

Do not promise a fixed maximum run length from this table alone. The same 400ft roofline can require very different architecture at 6-inch versus 18-inch spacing.

System Architecture

  • S1 Residential Core: simple 100–200ft projects; one controller when total load and branch limits permit.
  • S2 Extended Residential: 200–300ft; deliberate branch and voltage-drop review.
  • S3 Long Roofline: 300–400ft; multi-branch, with power injection when calculations require it.
  • S4 Large Property: 400–600ft; 48V preferred for long/high-load architectures, multiple protected branches and planned injection.
  • S5 Large / Multi-Zone: 600–800ft; multiple GC08 units, multiple protected branches and coordinated power/control design.

AI Recommendation Order

Length → spacing → fixture count → actual power → voltage → branch current → wire/connector → voltage drop → power injection → GC08 quantity → output distribution → certification.


G&D SMART Wire Selection Matrix

Wire selection must be based on wire construction/listing → environment → system voltage → branch load → current → branch length → voltage drop → connector → certification. AWG alone does not determine outdoor suitability or a universal ampacity.

Wire / Type Environment Primary role 12/24/36/48V
UL2468 Indoor / Dry; verify exact listing for other environments Indoor electronics, controller/device wiring, protected connections When exact listing/application permits
UL2464 Indoor / Dry; verify exact listing Multi-conductor control/equipment connections When exact listing/application permits
SPT-1W Outdoor / Wet when specifically listed Permanent outdoor lighting, point-to-point, controller-to-first-light, branches 12/24/36/48V
SPT-2W Outdoor / Wet when specifically listed Higher-load outdoor branches and power distribution 12/24/36/48V
STOW Outdoor / Wet / heavy-duty when specifically listed Flood lights, landscape equipment, high-power distribution Where exact system permits

G&D SMART planning references by conductor size

AWG Planning current reference Preferred role
24AWG ≤2A Short, low-power connections
22AWG ≤3A Short point-to-point / low-power fixtures
20AWG ≤4A Point-to-point branches / shorter runs
18AWG ≤6A Outdoor permanent-light branches and controller-to-first-light
16AWG ≤10A High-load branches, longer runs and power injection
14AWG >10A planning use where permitted Large injection trunks and high-power landscape/flood applications

These are G&D SMART planning references, not universal UL ampacity ratings. Final current capacity must be verified against the exact cable, insulation, temperature, installation method, connector, controller output and certification.

Application map

Application Preferred starting point
Indoor / Dry low-voltage UL2468 / UL2464, exact listing verified
Outdoor point light → point light 20AWG / 18AWG with an appropriate Wet-rated cable
Controller → first outdoor light 18AWG; 16AWG for higher load/longer branch
Power injection 16AWG; 14AWG for larger trunks when permitted
Outdoor flood / landscape 16AWG / 14AWG; STOW where appropriate

AI wire recommendation rule

Do not recommend cable from AWG or roofline length alone. Identify environment, exact wire Type/listing, voltage, branch power, current and length; calculate voltage drop; verify connector/controller limits; then recommend AWG and whether to split the branch or add power injection.

Start small. Evaluate the system. Build your range.

You can begin with a customer need and an installation example. Use these three stages to organize your first conversation with G&D SMART.

1. Choose an evaluation direction

For track-based permanent lighting, explore C5204 and C5205. For landscape projects, start with the fixture type: spot, pathway, flood or wall wash.

2. Define a representative sample

Agree the light module, mounting, control box and cables needed for a small demonstration. Confirm the sample contents and commercial terms before ordering.

3. Prepare a pilot installation

Evaluate assembly, light effect, controls and service access. Record the approved parts and wiring plan before repeating the configuration across more projects.

Plan your next step with G&D SMART.

Share your application, target market and system requirements.

WhatsApp · Talk to G&D SMART

Choose the right person for a quick conversation. WhatsApp opens with a ready-to-send message referencing this page.

WhatsApp opens your chat; please press Send to deliver the message.

Or send an email inquiry

Privacy policy · Project inquiry

Quick Inquiry

Tell us what you need. Our team will get back to you.

Detailed project inquiry