Technical Guides
How Far Can You Run 36V Permanent Outdoor Lights?
November 17, 2026
Quick answer: 36V can provide a useful long-run advantage because it reduces current compared with 24V for the same power. However, actual distance must be determined from real fixture, cable, connector, and voltage-drop performance rather than voltage alone.

Why 36V helps on long runs
Electrical current is calculated from:
Current = Power ÷ Voltage
For a 144W branch:
- 24V requires about 6A
- 36V requires about 4A
The lower current can reduce cable voltage drop and connector heating, which makes 36V attractive for long rooflines and professional installation systems.
G&D Smart 36V test conditions
G&D Smart evaluated a 36V permanent outdoor lighting system under the following practical conditions:
- 36V nominal system voltage
- 9-inch center-to-center fixture spacing
- Single-ended power feed
- Long continuous fixture string
- Professional permanent outdoor lighting architecture
150-fixture result
At 150 fixtures, the test measured approximately:
- Current: 3.93A
- Voltage at the final fixture: 27.8V
This represented a practical operating condition for the tested system.
200-fixture result
When the same single-ended architecture was extended to approximately 200 fixtures:
- Current: approximately 8.30A
- Voltage at the final fixture: approximately 10.5V
The final-fixture voltage had fallen dramatically and the current behavior had become abnormal. This was no longer an acceptable normal installation condition.
Why a larger power supply does not solve this
The problem was not simply total available wattage. The problem was the resistance of the long power-distribution path.
A larger power supply at the beginning of the run cannot eliminate resistance in:
- Wire
- Connectors
- Fixture conductors
- PCB traces
Once the branch becomes too long or current becomes too high, the correct solution is to redesign the power distribution.
Practical recommendation for the tested architecture
For this specific 36V configuration, approximately 130–150 fixtures per single-ended branch is a much more reasonable design range than 200–250 fixtures.
At 9-inch spacing:
150 fixtures × 9 inches = 1,350 inches
1,350 inches ÷ 12 = approximately 112.5 feet of illuminated length
This is not a universal 36V limit
Different products can produce different results because of:
- Fixture power
- Internal electronics
- Wire gauge
- Connector resistance
- PCB design
- Spacing
- Lead cable length
Therefore, the 130–150 fixture recommendation should be applied to the tested architecture, not automatically to every 36V product on the market.
Best use for 36V
36V works best as a long-run professional platform where reducing current is valuable and where the system's environmental rating and certification are compatible with the intended installation.
Installer takeaway
Do not judge a 36V system by asking whether the lights still turn on at 200 or 250 fixtures.
Judge it by measuring current, end voltage, connector temperature, and stable operation under maximum load.
That is the difference between a system that merely works during a test and one that is suitable for professional installation.

G&D Smart engineering perspective
G&D Smart develops professional permanent outdoor lighting systems for installers, regional lighting brands, distributors, and OEM/ODM partners in the United States and Canada. Our platform combines RGBW roofline fixtures, matched mounting profiles, controller and power-distribution hardware, cable and connector standards, and installer-oriented software.
This article is based on G&D Smart first-party electrical test data. Under the tested 36V, 9-inch, single-ended configuration, 150 fixtures measured 3.93A with 27.8V at the last light; extending to about 200 fixtures produced about 8.30A and only about 10.5V at the last light. That is why the practical recommendation is around 130–150 fixtures per branch for this tested architecture.
Related G&D Smart system components: C5204C 36V Roofline Lights and GC08 Control Box.
FAQ for installers and lighting brands
How many 36V lights does G&D Smart recommend per tested branch?
For the tested C5204-style 36V architecture at 9-inch spacing, approximately 130–150 fixtures per single-ended branch is the practical design range.
Does 36V eliminate the need for power distribution planning?
No. 36V reduces current compared with 24V for the same power, but long cable paths still create voltage drop and connector loading.
Technical content prepared by the G&D Smart Engineering Team. Final installation requirements must follow the listing, markings, instructions, local electrical requirements, and the exact components used in the project.
Supporting article image