Technical Guides
12V vs 24V vs 36V vs 48V Permanent Outdoor Lighting: Complete Test Data & Application Guide
November 09, 2026
Choosing between 12V, 24V, 36V and 48V permanent outdoor lighting is not simply a voltage comparison. The practical decision depends on measured full-output RGBW load, current, end-of-run voltage, cable and connector ratings, recommended continuous-run length, power-injection planning and the exact certification/environmental configuration.
This guide summarizes the supplied G&D SMART two-page comparison report for the C5204 RGBW point-light system. It reproduces the report's measured values and application recommendations. It is product-specific test information, not a universal rule for every LED fixture or installation.
Quick comparison: 12V vs 24V vs 36V vs 48V
| Specification | 12V | 24V | 36V | 48V |
|---|---|---|---|---|
| System voltage | 12V DC | 24V DC | 36V DC | 48V DC |
| IC / standard spacing | 2904 / 9in (229mm) | 2904 / 9in (229mm) | 2904 / 9in (229mm) | 2904 / 9in (229mm) |
| Cable specification in report | UL2468 / 20 AWG | UL2468 / 20 AWG | UL2468 / 18 AWG | UL2468 / 18 AWG |
| Waterproof connector in report | M12B / 5A | M12B / 5A | M12B / 10A | M12B / 10A |
| Recommended maximum continuous run | 60 lights | 120 lights | 200 lights | 300 lights |
Important: The 24V recommendation of 120 lights is an application recommendation in the source report, not a directly measured 120-light test point. The report contains 100- and 150-light measurements. Do not interpolate a 120-light result from those rows.
Full-output RGBW measured electrical data
The table below preserves the source report's exact test points. Input voltage, power, current and end voltage are shown for each available measurement. A dash means the source report does not provide a direct measurement at that lamp count.
| Light count | 12V system | 24V system | 36V system | 48V system |
|---|---|---|---|---|
| 50 | Input 12V 45.72W / 3.81A End 9.62V |
Input 24V 54.48W / 2.27A End 23.30V |
Input 36.3V 47.19W / 1.30A End 35.80V |
Input 48.3V 52.16W / 1.08A End 48.00V |
| 100 | — | Input 24V 108.10W / 4.50A End 21.00V |
Input 36.3V 93.29W / 2.57A End 34.70V |
Input 48.3V 100.46W / 2.08A End 47.10V |
| 150 | — | Input 24V 143.48W / 5.97A End 18.00V |
Input 36.3V 137.94W / 3.80A End 32.70V |
Input 48.3V 145.87W / 3.02A End 45.60V |
| 200 | — | — | Input 36.3V 194.57W / 5.36A End 29.90V |
Input 48.3V 193.20W / 4.00A End 43.40V |
| 250 | — | — | Input 36.3V 276.24W / 7.61A End 24.00V |
Input 48.3V 252.13W / 5.22A End 40.30V |
| 300 | — | — | — | Input 48.3V 312.02W / 6.46A End 35.70V |
| 350 | — | — | — | Input 48.3V 407.65W / 8.44A End 28.60V |
What the measured results tell installers
12V: compact layouts and short runs
The report recommends a maximum continuous run of 60 lights. Its measured reference at 60 lights is 51.24W, 4.27A and 9.01V end voltage. At equivalent power, a 12V arrangement carries higher current than a higher-voltage system, making cable, connector and voltage-drop planning especially important.
24V: a medium-size residential option
The report recommends 120 lights as the maximum continuous-run quantity. It records 108.10W / 4.50A with 21.00V at the end for 100 lights, and 143.48W / 5.97A with 18.00V at the end for 150 lights. There is no direct 120-light measurement in this report. Plan split feeds based on the actual route and full-output end-voltage test.
36V: larger professional installations
The report recommends 200 lights for a continuous run. At 200 lights, the recorded result is 194.57W / 5.36A with 29.90V end voltage. At 250 lights, the report records 276.24W / 7.61A and 24.00V end voltage, and recommends additional feed planning as the run approaches higher loads.
48V: longer runs and larger multi-zone layouts
The report recommends 300 lights as the continuous-run limit. At 300 lights, the measured result is 312.02W / 6.46A and 35.70V end voltage. The 350-light test records 407.65W / 8.44A and 28.60V end voltage; this is a tested point, not the recommended continuous-run quantity. The report's application summary states that the largest quantity tested was 400 lights, but the detailed matched-load table supplied here does not include a 400-light electrical row. Therefore, no 400-light power, current or end-voltage value is reproduced.
Signal distance and installation requirements
| Installation distance | 12V | 24V | 36V | 48V |
|---|---|---|---|---|
| Controller output to first light | 15m / 49.21ft | 15m / 49.21ft | 15m / 49.21ft | 15m / 49.21ft |
| Light to light | 5m / 16.40ft | 5m / 16.40ft | 5m / 16.40ft | 5m / 16.40ft |
These are the standardized signal-distance requirements stated in the supplied report. Keep signal-distance planning separate from power-injection planning: acceptable data communication does not by itself prove that end voltage or connector current is acceptable.
Power injection and T-connector planning
- 12V: Use shorter sections. Add a feed point when full-load testing shows the end voltage approaching the validated minimum or when visible brightness/color variation occurs.
- 24V: For longer runs, divide the system into separately fed sections. Determine feed spacing from full-RGBW end voltage and the actual cable route.
- 36V: For runs approaching the recommended quantity, check end voltage at full RGBW output before deciding feed locations. The 250-light test showed a 12.3V drop.
- 48V: 300 lights is the recommended continuous-run limit. For more than 300 lights, plan multiple feed points and separate sections. The 350-light test showed a 19.7V drop.
The report recommends placing a T-connector or branch at an engineered branch split or power-injection point. Check connector contact current and downstream cable capacity. For 36V and 48V, the report specifically calls for checking the M12B 10A connector and cable capacity together. With multiple power supplies, prevent reverse feeding between supplies and verify each branch.
A T-connector is not automatically a signal amplifier, a power supply or a substitute for branch protection. Use the approved wiring topology and connector pinout for the actual system.
Certification and installation environment
The report asks users to verify UL 2108 and cULus applicability against the exact certified models, components and complete system configuration. cULus is the dual-market certification mark for the United States and Canada, but its applicability must be checked against the actual product records.
Dry- and Damp-location suitability must be checked separately for the fixture, cable, waterproof connector, controller and power supply. Do not assume that one component's location rating automatically covers the complete system. This comparison does not establish Wet-location suitability.
How to use this comparison when selecting a system
- Identify the required continuous-run light count and physical cable route.
- Compare the recommended run quantity with the measured full-output test points.
- Check end voltage, current, cable gauge and connector rating together.
- Plan feed points and branches using the actual installation drawing.
- Confirm the exact model's certification and Dry/Damp suitability for every component.
- Record the approved configuration before ordering or commissioning.
Download the Complete G&D SMART Comparison Report
Download the original two-page technical report for the complete electrical test matrix and installation/application comparison across 12V, 24V, 36V and 48V C5204 RGBW systems.
PDF: G&D SMART 12V / 24V / 36V / 48V Complete Application Comparison (English)
The original two-page G&D SMART comparison report includes the electrical test matrix and the installation, signal-distance, power-injection, T-connector and certification-environment comparison. The original PDF is available from the download link above.
Frequently asked questions
Which voltage supports the longest recommended continuous run in this report?
The report recommends 48V for up to 300 lights in a continuous run. This is a product-specific application recommendation, not a universal limit for all 48V lighting products.
Is 350 lights the recommended 48V run?
No. The report includes a 350-light test point, but recommends 300 lights as the maximum continuous run. The 350-light result has a 28.60V end voltage.
Was 120 lights directly tested on the 24V system?
No. The report recommends 120 lights but provides direct measurements at 100 and 150 lights only.
What signal cable distances does the report specify?
15m (49.21ft) from controller output to first light, and 5m (16.40ft) between lights, for all four voltage systems.
Does this report prove every component is cULus certified?
No. The report explicitly says certification applicability must be confirmed against the exact certified models, components and complete system configuration.
Report basis and limitations
All electrical measurements, specifications and application recommendations above are transcribed from the supplied G&D SMART document, “12V / 24V / 36V / 48V — Complete Electrical & Load Comparison” and “Installation, Signal Transmission & Certification Environment Comparison” (two pages). The report combines product-specific test results and internal engineering application recommendations; it is not a universal industry standard. Missing test points are left blank and are not estimated or interpolated.
Discuss your voltage and installation requirements with G&D SMART.